CVE-2021-32986 Detail

Awaiting Analysis


This vulnerability is currently awaiting analysis.

Description

After Automation Direct CLICK PLC CPU Modules: C0-1x CPUs with firmware prior to v3.00 is unlocked by an authorized user, the unlocked state does not timeout. If the programming software is interrupted, the PLC remains unlocked. All subsequent programming connections are allowed without authorization. The PLC is only relocked by a power cycle, or when the programming software disconnects correctly.

Severity

CVSS 3.x Severity and Metrics:

CVSS 2.0 Severity and Metrics:

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to [email protected].

Weakness Enumeration

CWE-ID CWE Name Source
CWE-288 Authentication Bypass Using an Alternate Path or Channel ICS-CERT  

Change History

0 change records found show changes

Quick Info

CVE Dictionary Entry:
CVE-2021-32986
NVD Published Date:
04/04/2022
NVD Last Modified:
04/05/2022
Source: